[Intermediate] — Reading a step response, the two numbers that determine everything, and the specifications you design against.
First-order systems
Step response:
y
K ┤ ╭────────────────────
│ ╭─╯
│ ╭─╯
│ ╭─╯
│ ╱
0 ┼╯────┬────┬────┬────┬──────→ t
0 τ 2τ 3τ 4τ
63% 86% 95% 98%
One parameter, , determines everything. Reach 63% in one time constant, 98% in four. Settling time ≈ is the rule of thumb worth memorising.
No overshoot, no oscillation, ever. A first-order system cannot overshoot — which is why thermal processes and simple RC filters are so well-behaved and so slow.
Second-order systems
Two parameters, and they do completely different jobs:
- — natural frequency. How fast. Scales the time axis
- — damping ratio. Shape. Determines overshoot and oscillation
The poles:
| Poles | Response | |
|---|---|---|
| imaginary | undamped — oscillates forever | |
| complex pair | underdamped — overshoots, then settles | |
| repeated real | critically damped — fastest with no overshoot | |
| two distinct real | overdamped — slow, no overshoot |
y
│ ╭╮ ζ = 0.2 (oscillatory)
│ ╱ ╲╭─╮
1 ┼────╱────╰─╰──────────
│ ╱ ╭─────────── ζ = 0.7 (good compromise)
│ ╱ ╱ ╭────────── ζ = 1.0 (critical)
│ ╱ ╱ ╱ ╱ ζ = 2.0 (sluggish)
0 ┼╯─┴─┴─┴────────────→ t
is the classic design target. About 5% overshoot, fast settling, and reasonable robustness. has no overshoot but is slower to settle than — which surprises people. Critically damped is fastest to reach the target monotonically, not fastest to settle within a band.
The geometric reading of pole location is worth internalising, because it’s what makes root locus design intuitive:
Im
│ ×
│ ╱│
│ ╱ │ ωd = ωn√(1−ζ²)
ωn│ ╱ │
│╱ θ │
──────────┼────┼───── Re
−ζωn
- Distance from origin = (speed)
- Angle from the negative real axis = (damping)
- Horizontal distance = (decay rate — this sets settling time)
- Vertical distance = (oscillation frequency)
Move a pole left → faster settling. Move it toward the real axis → less overshoot. That’s the entire vocabulary of pole placement.
Step response specifications
The numbers you actually design against:
The overshoot table is worth carrying:
| Overshoot | |
|---|---|
| 0.3 | 37% |
| 0.5 | 16% |
| 0.7 | 4.6% |
| 0.8 | 1.5% |
| 1.0 | 0% |
Two things fall out of these formulas that shape how you design:
Overshoot depends only on . Not on . So you set damping to meet the overshoot spec, then set to meet the speed spec — the two requirements decouple, which is unusually convenient.
Settling time depends on , the real part of the pole. That’s why “move the poles left” means “settle faster”.
Dominant poles
Real systems are higher than second order. The approximation that makes classical design work:
Poles far to the left decay fast and contribute little. The behaviour is dominated by the poles closest to the imaginary axis.
Rule of thumb: if other poles are 5× further left, treat the system as second-order using the dominant pair.
Im
│ × ← dominant pair
× │ (these determine the response)
──────┼────── Re
× │ ×
↑
fast poles — negligible
This is why every textbook formula above, derived for a pure second-order system, applies usefully to a sixth-order plant. It’s also the first thing to check when a system doesn’t behave as designed — a neglected pole or an unmodelled delay has crept close enough to matter.
Steady-state error
Does the output actually reach the reference? For unity feedback with loop gain :
The answer depends on the system type — the number of integrators ( terms) in :
| Type | Step input | Ramp input | Parabola |
|---|---|---|---|
| 0 (no integrator) | ∞ | ∞ | |
| 1 (one integrator) | 0 | ∞ | |
| 2 (two integrators) | 0 | 0 |
Each integrator in the loop eliminates the steady-state error to one higher order of input. That is precisely why the I term in a PID controller kills steady-state error — it adds an integrator, taking the system from type 0 to type 1. → PID Control
And it explains a common frustration: a proportional-only controller on a plant with no natural integrator will always have a steady-state offset. Raising the gain shrinks it but never removes it — you need the integrator.
Where the integrator comes from doesn’t matter. A motor position loop is naturally type 1 (velocity integrates to position), so P control alone gives zero steady-state position error. A motor speed loop is type 0, and needs the I term.
Time delay
The most destructive thing you can have in a loop.
Unity magnitude at every frequency, and phase lag growing without bound: radians.
So delay costs you phase margin — the thing keeping you stable — while giving nothing back. → Frequency Response
Because isn’t rational, it’s often approximated for analysis by a Padé approximation:
Note the numerator — that’s a right-half-plane zero. Delay behaves like a non-minimum-phase element, with all the bandwidth limitations that implies. → RHP zeros
Sources of delay in real systems, all of which count:
- Transport lag (fluid down a pipe, material on a conveyor)
- Sensor processing and filtering
- Computation time
- Sampling — a zero-order hold adds an average delay of half a sample period → Digital Control
- Network latency, in distributed control
Delay is why the shower oscillates. You adjust the tap, wait, feel no change, adjust more, and then both adjustments arrive at once. It’s also why cloud autoscaling oscillates — instances take minutes to boot, so the controller keeps scaling while the previous action is still in flight.
Smith predictor is the classical remedy: use a model to predict what the delayed output will be and control against the prediction. Works well when the delay is known and constant, and badly when it isn’t.
Reading a real step response
The practical skill — extracting a model from data:
y │ ╭─╮___________
│ ╭─╯ ╰
│ ╱
│ ╱
│ ╱
│__╱
└──┬─────────────────→ t
└─ dead time θ
- Dead time — the flat bit before anything happens. Pure delay
- Slope and time constant — draw the maximum-slope tangent; where it crosses the final value gives
- Final value ÷ step size = DC gain
- Overshoot → from the table above
- Oscillation period → , hence
That gives you or a second-order fit — enough to design a controller. This is what Ziegler–Nichols open-loop tuning is doing, and it’s why a step test is the first thing you do to an unfamiliar plant. → PID Control
The ratio is the single most useful number from that test: below ~0.2 the loop is easy to control, above ~1 it’s genuinely difficult and no amount of PID tuning will make it fast.
Related
- Modelling and Transfer Functions — where poles come from
- PID Control — using this to tune
- Stability and Root Locus — moving poles deliberately
- Control theory map